Results

For 3.18 kWh/day you need about 2.7 kWp of panels (6 × 450 W), a 15.4 kWh LiFePO₄ (LFP) bank at 48 V and a 4 kW inverter. The design month is December, when each kWp delivers only 1.76 kWh/day.
Solar array
2.7kWp
6 × 450 W panels at 55°
Battery bank
15.4kWh
300 Ah @ 48 V · usable 11.6 kWh
Battery configuration
4S × 3P
12 × 12.8 V 100 Ah units
Inverter
4kW
continuous; surge ≥ 4.4 kW
Charge controller
80 A
MPPT · 70 A needed at 48 V
Daily load
3.18kWh/day
3.81 kWh/day from the battery bus, incl. inverter losses
Design month
Dec
2.12 kWh/m²/day on panels (sun-hours)
Real autonomy
3days
temperature factor 94%
Months needing backup
0/ 12
none
Summer surplus (unused)
1,666kWh/yr
typical for winter-sized arrays
Battery life
15years
about 68 cycles/yr · rated 6,000 cycles, 15 yr calendar
Rough system cost
€10,937
hardware + install estimate
Daily solar harvest vs. daily need, by month
Array size needed if designed for each month
Where the energy goes

Monthly energy balance (★ = design month)

MonthSun on panels (kWh/m²/day)Solar (kWh/day)Need (kWh/day)Coverage
Jan2.455.513.94140%
Feb3.397.483.94190%
Mar4.239.053.94230%
Apr4.8310.033.94255%
May510.143.94258%
Jun5.029.993.94254%
Jul5.2810.373.94264%
Aug5.4510.73.94272%
Sep4.889.873.94251%
Oct48.43.94214%
Nov2.575.633.94143%
Dec2.124.763.94121% ★

Load list

LoadWh/dayShare
Lighting32010%
Refrigeration80025%
TV / entertainment2408%
Computers3009%
Always-on devices2408%
Water pump75024%
Washing machine2297%
Other3009%

Component checklist

ComponentSpecification
PV array6 × 450 W = 2.7 kWp, 55° tilt, azimuth 180°
Battery bank12 × 12.8 V 100 Ah (4 in series × 3 parallel) = 15.4 kWh, LiFePO₄ (LFP)
Charge controllerMPPT, ≥ 70 A at 48 V (PV string Voc must stay below its max input voltage)
Inverter4 kW continuous pure-sine, 48 V DC input, surge ≥ 4.4 kW
Battery cable & fusesized for about 81 A continuous
  • Sun: NASA POWER long-term monthly climate at 44.43, 26.1 (embedded default-site data for pre-rendering), on panels at 55° / 180°, with cell temperature and 12% PV losses.
  • Energy chain: AC loads ÷ 92% inverter efficiency + 15 W idle draw → battery bus. 60% of it cycles through the battery at 95% round-trip efficiency; controller efficiency is 97%.
  • Days of autonomy cover consecutive cloudy days. NASA monthly means don’t show multi-day storms, so remote critical systems often use 3–5 days and a generator.