Results

You need ≈ 13.8 kWh nominal (288 Ah at 48 V). With 12.8 V 100 Ah units: 4 in series × 3 in parallel = 12 units, 15.36 kWh.
Configuration
4S3P
12 × 12.8 V 100 Ah
Required capacity
13.8kWh
288 Ah at 48 V
Installed bank
15.36kWh
300 Ah at 51.2 V
Usable energy (new)
11.2kWh
80% DoD, temp. 94%
Actual autonomy (end of life)
1.7days
target 1.5 days
Peak discharge current
63A
0.21C · bank limit 300 A
Units in series
4
12.8 V × 4 = 51.2 V
Parallel strings
3
fuse each string
How the required capacity builds up
Units needed vs. days of autonomy

Same requirement at other system voltages

SystemLayoutUnitskWhAh neededPeak AStatus
12 V1S11P1114.081,152252OK
24 V2S6P1215.36576126OK
48 V4S3P1215.3628863OK

Sizing steps

StepWh
Daily energy at battery terminals5,376
× days of autonomy8,065
÷ discharge efficiency8,314
÷ depth of discharge10,392
÷ temperature factor11,056
÷ end-of-life capacity13,820
  • Series: voltages add, Ah stay the same. Parallel: Ah add, voltage stays the same. Always use identical units of the same age; connect parallel strings with equal cable lengths (diagonal or busbar wiring) and fuse each string.
  • Lithium banks need a BMS per series string; DIY cell packs need a balancer and cell-level fusing.