Batteries & storage calculator

Battery bank size calculator: capacity, Ah and series/parallel wiring

Works out how many kWh and amp-hours your battery bank needs (with margins for depth of discharge, temperature, ageing and efficiency) and how to wire your chosen batteries in series and parallel.

Editable share link Branded PDF report Free · no sign-up

Results

You need ≈ 13.8 kWh nominal (288 Ah at 48 V). With 12.8 V 100 Ah units: 4 in series × 3 in parallel = 12 units, 15.36 kWh.
Configuration
4S3P
12 × 12.8 V 100 Ah
Required capacity
13.8kWh
288 Ah at 48 V
Installed bank
15.36kWh
300 Ah at 51.2 V
Usable energy (new)
11.2kWh
80% DoD, temp. 94%
Actual autonomy (end of life)
1.7days
target 1.5 days
Peak discharge current
63A
0.21C · bank limit 300 A
Units in series
4
12.8 V × 4 = 51.2 V
Parallel strings
3
fuse each string
How the required capacity builds up
Units needed vs. days of autonomy

Same requirement at other system voltages

SystemLayoutUnitskWhAh neededPeak AStatus
12 V1S11P1114.081,152252OK
24 V2S6P1215.36576126OK
48 V4S3P1215.3628863OK

Sizing steps

StepWh
Daily energy at battery terminals5,376
× days of autonomy8,065
÷ discharge efficiency8,314
÷ depth of discharge10,392
÷ temperature factor11,056
÷ end-of-life capacity13,820
  • Series: voltages add, Ah stay the same. Parallel: Ah add, voltage stays the same. Always use identical units of the same age; connect parallel strings with equal cable lengths (diagonal or busbar wiring) and fuse each string.
  • Lithium banks need a BMS per series string; DIY cell packs need a balancer and cell-level fusing.

How this battery bank calculator works

Sizing a battery bank is a chain of corrections. You start from the energy your loads need and end with a nominal capacity that is noticeably larger, because a battery must never be emptied completely, delivers less when cold, loses some energy as heat and shrinks as it ages. This calculator applies each correction step by step (the bar chart shows how the requirement grows) and then turns the result into a real wiring plan for the battery or cell you have chosen.

  1. Energy at the battery: daily energy divided by inverter efficiency if the loads are AC.
  2. Autonomy: multiplied by the days the bank must carry the loads without recharging.
  3. Discharge efficiency: a few percent are lost inside the battery (about 3% for LFP, 10% for lead-acid).
  4. Depth of discharge: only part of the capacity may be used: 80–90% for LFP, about 50% for lead-acid.
  5. Temperature: capacity drops in the cold, roughly 1% per °C below 25 °C for lead-acid and 0.4% for lithium.
  6. Ageing: an end-of-life margin (IEEE 485 ageing factor) keeps the bank adequate when worn.

The result is divided by the system voltage to give amp-hours. The calculator then puts enough units in series to reach the system voltage and enough strings in parallel to reach the capacity, and checks the bank’s current rating against your peak load.

The formulas

E_req = (E_day ÷ η_inv) × days ÷ η_batt ÷ DoD ÷ k_temp ÷ k_EOL Ah_req = E_req ÷ V_system N_series = V_system ÷ V_unit N_parallel = ⌈ E_req ÷ (V_bank × Ah_unit) ⌉ I_peak = P_peak ÷ η_inv ÷ V_bank ≤ N_parallel × I_max,unit

Worked example: 48 V off-grid home bank

The defaults ask for 5 kWh a day from the battery through a 93%-efficient inverter, with 1.5 days of autonomy, LFP batteries used to 80% DoD, a lowest operating temperature of 10 °C and an 80% end-of-life design point.

The chain runs: 5.38 kWh/day at the terminals → 8.06 kWh for 1.5 days → 8.31 kWh after discharge losses → 10.4 kWh at 80% DoD → 11.1 kWh at 10 °C → 13.8 kWh nominal, or 288 Ah at 48 V. With 12.8 V 100 Ah LFP batteries the plan is 4S3P: four in series for 51.2 V, three strings in parallel for 300 Ah. That is twelve batteries and 15.36 kWh. A 3 kW peak load draws 63 A, well within the 300 A the three strings can supply, and the bank still delivers 1.7 days of autonomy at end of life.

The same requirement at 12 V would need eleven batteries in parallel and 252 A of peak current, a clear argument for 48 V.

How to read the results

  • Configuration (e.g. 4S3P) is the wiring plan: series units per string × parallel strings.
  • Installed bank is usually a little larger than required because batteries come in whole units.
  • Actual autonomy (end of life) shows the real margin after rounding up.
  • Peak discharge current and C-rate: lead-acid batteries are happiest below about 0.2C, LFP below 0.5–1C (check the BMS rating).

Typical bank sizes

Application Daily energy Autonomy Typical bank (LFP) Typical bank (lead-acid)
Van / small boat 1–2 kWh 1 day 12 V 100–200 Ah 12 V 200–400 Ah
Weekend cabin 1.5–3 kWh 1.5–2 days 24 V 150–300 Ah 24 V 300–600 Ah
Off-grid home 4–10 kWh 1.5–3 days 48 V 200–600 Ah 48 V 500–1,500 Ah
Home backup (essentials) 3–6 kWh 0.5–1 day 5–10 kWh at 48 V rarely used today

Tips

  • Use identical batteries of the same model, capacity and age in one bank; never mix chemistries.
  • Wire parallel strings symmetrically. Take the positive from one end and the negative from the other, or use busbars, so every string sees the same cable resistance.
  • Fuse every parallel string close to the battery; a short in one string can otherwise be fed by all the others.
  • Go to a higher system voltage before adding strings. Fewer parallel strings means fewer fuses, better balance and thinner cables (see the cable size calculator).
  • Check runtime at real loads with the battery backup time calculator, and the charging side with the off-grid solar calculator.

Limitations

The calculator treats the daily energy as an average; if short, very high loads dominate, check the battery’s power rating and Peukert losses separately. Temperature factors are simple linear approximations, and lithium charging limits below 0 °C are not modelled. Battery-management-system settings, cell balancing and manufacturer-specific parallel limits always take precedence over these general rules.

Method & assumptions

Required nominal energy = daily energy ÷ inverter efficiency × days of autonomy ÷ battery discharge efficiency ÷ depth of discharge ÷ temperature factor ÷ end-of-life capacity (IEEE 485-style ageing margin). Required Ah = Wh ÷ system voltage.

Series count = system voltage ÷ unit voltage; parallel strings = ⌈ required Wh ÷ (bank voltage × unit Ah) ⌉. Peak current = peak load ÷ inverter efficiency ÷ bank voltage, compared with parallel strings × the unit's continuous current limit.

Frequently asked questions

How do I calculate the battery bank size I need?
Take the daily energy drawn from the battery (kWh), divide by inverter efficiency, multiply by days of autonomy, then divide by the usable depth of discharge, a temperature factor and an end-of-life margin. For 5 kWh/day, 1.5 days, LFP at 80% DoD, 10 °C and 80% end-of-life capacity, that gives about 13.8 kWh nominal — 288 Ah at 48 V.
How many batteries do I need for a 48 V system?
Series count = 48 ÷ unit voltage: four 12 V (12.8 V LFP) batteries, eight 6 V batteries, sixteen 3.2 V LFP cells or twenty-four 2 V cells form one 48 V string. Then add identical strings in parallel until the bank reaches the required amp-hours. A bank written 4S3P means 4 in series, 3 strings in parallel — 12 batteries.
What is the difference between wiring batteries in series and parallel?
Series connections add voltages while the amp-hour capacity stays the same (two 12 V 100 Ah batteries make 24 V 100 Ah). Parallel connections add amp-hours at the same voltage (two 12 V 100 Ah make 12 V 200 Ah). Both double the stored energy — 2.4 kWh in either case — but higher voltage halves the current for the same power.
How many parallel strings of batteries is too many?
For lead-acid, most manufacturers recommend no more than three or four parallel strings, because small differences in cable resistance and cell ageing make strings share current unevenly. Lithium batteries with their own BMS tolerate more, but beyond about eight strings a higher-capacity battery or rack system is easier to protect and balance.
Should I choose 12 V, 24 V or 48 V for my battery bank?
Choose by power: up to about 1–1.5 kW, 12 V works; 1.5–3 kW suits 24 V; above that use 48 V. A 3 kW inverter draws about 270 A at 12 V but only 68 A at 48 V, so cables, fuses and losses all shrink as voltage rises.
What is an ageing factor in battery sizing?
IEEE 485 recommends sizing stationary batteries with an ageing factor of 1.25, so the bank still meets the load when its capacity has faded to 80% at end of life. Without it, a battery that is just big enough on day one will fall short after a few years.

Sources & references

  1. IEEE Std 485: Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications
  2. IEEE Std 1562: Guide for Array and Battery Sizing in Stand-Alone PV Systems
  3. Battery University: BU-302 Series and parallel battery configurations
  4. Sandia National Laboratories: Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices

Embed this calculator

Free for blogs, installers, schools and NGOs. Copy the code below; it updates itself automatically.