Batteries & storage calculator

Battery backup time calculator: how long will my battery last?

Runtime of any battery (power station, home battery, UPS or 12 V bank) from capacity, depth of discharge, inverter losses, temperature and age, with Peukert’s law for lead-acid batteries.

Editable share link Branded PDF report Free · no sign-up

Results

About 18 h 11 min at 210 W. That covers your 12-hour target.
Backup time
18 h 11 min
210 W load · 0.8 days
Usable energy
4.61kWh
5.12 kWh nominal × 90% DoD
Battery drain
253W
incl. 11% inverter loss + 20 W idle
Discharge current
19.8A
0.05C at 12.8 V
Runtime without Peukert
18 h 11 min
lithium: negligible
Energy delivered to loads
3.82kWh
Capacity for 12 h
3.3kWh
256 Ah at 12.8 V nominal
Temperature / age factor
100%
25 °C, 100% health
Runtime vs. load
Load breakdown

Runtime at other loads

LoadBattery drain (W)Current (A)RuntimeC-rate
25 W483.796 h 27 min0.01C
50 W765.960 h 59 min0.01C
100 W13110.235 h 09 min0.03C
200 W24218.919 h 01 min0.05C
300 W35327.613 h 02 min0.07C
500 W576458 h 00 min0.11C
750 W85366.75 h 24 min0.17C
1,000 W1,13188.44 h 04 min0.22C
1,500 W1,687131.82 h 41 min0.33C
2,000 W2,242175.22 h 00 min0.44C
3,000 W3,3532621 h 20 min0.65C

Selected loads

DeviceAverage WShare
Refrigerator6029%
Wi-Fi router + modem157%
LED lighting (5 bulbs)4521%
TV 50"9043%
  • Average power matters, not nameplate power: a fridge rated 150 W cycles on and off and averages 40–80 W; start-up surges affect inverter size, not runtime.
  • Lithium batteries keep nearly full capacity at moderate currents, so Peukert effects are minimal (k ≈ 1.02–1.05).

How this battery runtime calculator works

“How long will my battery last?” sounds like simple division (capacity over load), but the naive answer is often 30–50% too optimistic. This calculator accounts for every factor that shortens real runtime:

  • Depth of discharge (DoD). Lithium iron phosphate (LFP) batteries can use 80–100% of their capacity; lead-acid batteries should stop at about 50% to avoid rapid ageing.
  • Inverter losses. Running AC appliances from a battery costs 7–15% in conversion, plus the inverter’s own idle consumption every hour it is switched on.
  • Peukert’s law. Lead-acid batteries deliver less charge at high currents. The calculator applies Peukert’s equation relative to the battery’s rated discharge time (20 hours for most lead-acid ratings).
  • Temperature and age. Capacity falls in the cold (roughly 1% per °C below 25 °C for lead-acid) and as batteries age; end-of-life is usually defined at 70–80% of original capacity.

Pick the devices you want to keep running in an outage, or enter your own total, and the calculator returns the runtime, the current and C-rate, a runtime curve for other loads, and the battery size you would need for your target backup time.

The formulas

E_usable = Ah × V × n × DoD × SoH × k_temp (or kWh × n × …) P_battery = P_load ÷ η_inverter + P_idle (DC loads: P_battery = P_load) Lithium: t ≈ E_usable ÷ P_battery Lead-acid: t = H × [ C ÷ (I × H) ]^k × DoD, I = P_battery ÷ V C-rate = I ÷ C

Here H is the rated discharge time (20 h), C the effective capacity in Ah and k the Peukert exponent (1.1–1.3 for lead-acid, about 1.03 for LFP).

Worked example: two 200 Ah LFP batteries in a power outage

The defaults describe two 12.8 V 200 Ah LiFePO₄ batteries in parallel (5.12 kWh nominal, 4.61 kWh usable at 90% DoD) powering a fridge (60 W average), router (15 W), LED lighting (45 W) and a 50-inch TV (90 W): 210 W in total. Through a 90%-efficient inverter with 20 W idle draw, the battery supplies 253 W, a gentle 0.05C. Runtime is about 18 hours 11 minutes, comfortably above the 12-hour target.

Swap in two 12 V 200 Ah AGM batteries and the picture changes: usable energy halves to 2.4 kWh at 50% DoD and runtime falls to about 9 hours 24 minutes. At a 1,000 W load the AGM bank lasts only 1 hour 41 minutes — 21% less than simple division suggests, because Peukert’s law penalises the 94 A discharge current.

How to read the results

  • Backup time is the time to reach your DoD limit, not to a completely flat battery.
  • Battery drain shows how much the inverter adds. If its idle draw is a large share of a small load, DC appliances or a smaller inverter extend runtime noticeably.
  • C-rate above the chemistry’s comfortable limit (about 0.2–0.3C for lead-acid, 1C for LFP) triggers a warning.
  • Capacity for target sizes the battery bank you would need, Peukert and temperature included. Refine the configuration with the battery bank size calculator.

Typical runtimes (12 V 100 Ah = 1.2 kWh nominal, via inverter)

Load LFP (90% DoD) AGM (50% DoD)
Router + modem (15 W) ≈ 30 h ≈ 17 h
CPAP without humidifier (40 W, DC) ≈ 29 h ≈ 16 h
Fridge average (60 W) ≈ 13 h ≈ 6.5 h
Essentials 200 W ≈ 4.7 h ≈ 2 h
Microwave 1,000 W ≈ 1 h ≈ 20 min

Values include a 90% inverter and 20 W idle (except the DC CPAP); real figures vary with battery age and temperature.

Tips to extend backup time

  • Know your average loads. A fridge or freezer label shows its maximum; its average over a day is typically a third to a half. Measure with a plug-in energy meter or use the appliance energy cost calculator.
  • Switch off the inverter when nothing AC is needed, or run routers, lights and CPAPs directly from 12 V.
  • Keep batteries warm. A battery in an unheated garage at 0 °C can lose 10–25% of capacity.
  • Don’t oversize the inverter. A 3 kW inverter idling at 40 W can consume more than the router you want to keep online.
  • Recharge with solar. Even a few hundred watts of panels can extend an outage indefinitely in summer; see the off-grid solar calculator.

Limitations

Real batteries show voltage sag near empty, which may trip an inverter’s low-voltage cut-off before the nominal DoD is reached. Peukert’s law is an empirical approximation valid over moderate current ranges; at very low currents it overpredicts capacity, so the calculator caps the gain at 15% for lead-acid. Battery-management-system limits, cell imbalance and ambient temperature changes during discharge are not modelled. Battery packs whose capacity is given in mAh at 3.6–3.7 V (power banks) should be converted to Wh first.

Method & assumptions

Usable energy = nominal capacity (Ah × V × number, or kWh) × depth of discharge × state of health × temperature factor (lead-acid ≈ −1%/°C below 25 °C, lithium ≈ −0.4%/°C). Battery drain = load ÷ inverter efficiency + inverter idle power (for AC loads).

Runtime (Peukert's law): t = H × [C ÷ (I × H)]^k × DoD, where C is the effective Ah capacity, I = drain ÷ battery voltage, H the rated discharge hours (20 h for lead-acid) and k the Peukert exponent. For lithium, k is near 1 and runtime ≈ usable Wh ÷ drain W.

Frequently asked questions

How long will a 100Ah battery last?
A 12 V 100 Ah battery stores 1.2 kWh. A lithium (LFP) battery can deliver about 90% of that, so at a 100 W load through an inverter (about 130 W drawn from the battery including losses) it lasts roughly 8.5–9 hours. A lead-acid battery should only be discharged to 50%, giving about 4 hours at the same load — and less at high loads because of the Peukert effect.
How do I calculate battery runtime?
Runtime (hours) = usable battery energy (Wh) ÷ power drawn from the battery (W). Usable energy = Ah × V × depth of discharge × health × temperature factor. Power drawn = load ÷ inverter efficiency + inverter idle power. For lead-acid batteries, correct for Peukert's law because their capacity falls at high discharge currents.
How long can a 10 kWh battery power a house?
With 95% usable capacity and an efficient inverter, a 10 kWh home battery supplies about 9 kWh. Essential loads (fridge, router, lights, TV, about 200–300 W) run for 30–40 hours; an average house drawing 1 kW runs about 8–9 hours; electric heating, ovens or air conditioning drain it in a few hours.
What is the Peukert effect?
Peukert's law describes how a battery's effective capacity shrinks as the discharge current grows. It matters for lead-acid batteries (exponent 1.1–1.3): a 100 Ah AGM battery rated over 20 hours may deliver only 70–80 Ah when discharged in two hours. Lithium batteries have exponents of about 1.02–1.05, so the effect is negligible.
Why does my battery last less than the calculation?
The most common reasons are nameplate instead of average load (motors and compressors cycle), inverter idle draw (10–50 W, 24 hours a day), cold temperatures, an aged battery (capacity falls to 70–80% at end of life), and lead-acid batteries discharged at high current. Enter these in the advanced options.
What size battery do I need for 24 hours of backup?
Multiply the average power drawn from the battery by 24 h and divide by the usable depth of discharge. For a 250 W drain that is 6 kWh usable, or about 6.7 kWh of lithium (90% DoD) or 12 kWh of lead-acid (50% DoD). The 'capacity for target' tile computes this including Peukert and temperature effects.

Sources & references

  1. Peukert, W. (1897). Über die Abhängigkeit der Kapazität von der Entladestromstärke bei Bleiakkumulatoren. Elektrotechnische Zeitschrift 20
  2. Battery University: BU-503: How to calculate battery runtime; BU-502: Discharging at high and low temperatures
  3. IEEE Std 1188 / IEEE 485: Sizing and maintenance of lead-acid batteries for stationary applications