Results

100 kVA at power factor 0.8 = 80 kW. A 33.7 kVAr capacitor bank would lift the power factor to 0.95, cutting current from 144 A to 122 A (−29% cable losses) and freeing 15.8 kVA of capacity.
Real power
80kW
power factor 0.8
Apparent power
100kVA
Reactive power
60kVAr
Line current (per phase)
144.3A
I = S ÷ (√3 × 400 V)
Phase angle φ
36.9°
Power in horsepower
107.3hp
Capacitor bank for PF 0.95
33.7kVAr
Current after correction
121.5A
−16% current
kVA after correction
84.21kVA
Power triangle (before → after correction)
Current vs power factor (same kW)

Same apparent power at other power factors

Power factorkWkVArCurrent (A)
11000144.3
0.959531.22144.3
0.99043.59144.3
0.858552.68144.3
0.88060144.3
0.757566.14144.3
0.77071.41144.3

Standard generator / transformer sizes at PF 0.8

kVAkWAmps @ 400 V 3-ph
10814
201629
302443
504072
635091
10080144
160128231
250200361
400320577
630504909
1,0008001,443
1,6001,2802,309
2,5002,0003,608
  • kVA is what cables, transformers and generators must carry; kW is the power that does useful work. The ratio is the power factor.
  • Generators are usually rated in kVA at 0.8 PF, so a 100 kVA genset delivers at most 80 kW of real power.
  • Capacitor sizing assumes a sinusoidal supply. With many drives or inverters (harmonics), use detuned capacitor banks or active filters and have an engineer check for resonance.

Free calculator by GreenEnergy.net