How this kVA to kW calculator works
Alternating-current circuits carry two kinds of power. Real (active) power, in kW, does useful work: heat, light, motion. Reactive power, in kVAr, sloshes back and forth to build the magnetic fields of motors and transformers and does no net work. Their vector sum is the apparent power, in kVA, which determines the current that cables, switchgear, transformers and generators must carry. The ratio kW ÷ kVA is the power factor (cos φ).
Enter whichever quantity you know (kVA, kW or current) with the power factor, system type (single-phase, three-phase or DC) and voltage. The calculator returns all the others, draws the power triangle, shows how current rises as power factor falls and sizes the capacitor bank needed to correct the power factor to a target value.
The formulas
Worked example: a 100 kVA generator
The default is a 100 kVA three-phase generator at 400 V with the industry-standard rating power factor of 0.8:
- Real power: 100 × 0.8 = 80 kW
- Reactive power: 100 × sin(36.9°) = 60 kVAr
- Current: 100,000 ÷ (1.732 × 400) = 144 A per phase
If the site’s load really ran at PF 0.8, a 33.7 kVAr capacitor bank would lift it to 0.95. The same 80 kW would then need only 84.2 kVA and 122 A. That is 16% less current and about 29% lower cable losses (losses scale with current squared), freeing 16 kVA of generator or transformer capacity.
How to read the results
- The power triangle: the horizontal leg is kW, the vertical leg kVAr, the hypotenuse kVA. The dashed line shows the kVA after correction: same kW, shorter hypotenuse.
- Current vs power factor: for the same useful power, current rises steeply below PF 0.8; this is what utilities penalise.
- Standard sizes table: kW and amps for common generator and transformer ratings at PF 0.8 and your voltage.
Typical power factors
| Load | Power factor |
|---|---|
| Resistive heaters, kettles, incandescent lamps | 1.00 |
| EV chargers, modern PSUs with PFC, PV inverters | 0.95–1.00 |
| LED lighting (quality drivers) | 0.90–0.98 |
| Induction motor, full load | 0.80–0.90 |
| Induction motor, half load | 0.65–0.80 |
| Induction motor, no load | 0.20–0.40 |
| Welding transformers, arc furnaces | 0.50–0.70 |
| Typical industrial site, uncorrected | 0.70–0.85 |
Amps for common kVA ratings (three-phase)
| kVA | kW at PF 0.8 | Amps at 400 V | Amps at 480 V | Amps at 208 V |
|---|---|---|---|---|
| 20 | 16 | 29 | 24 | 56 |
| 50 | 40 | 72 | 60 | 139 |
| 100 | 80 | 144 | 120 | 278 |
| 250 | 200 | 361 | 301 | 694 |
| 500 | 400 | 722 | 601 | 1,388 |
| 1,000 | 800 | 1,443 | 1,203 | 2,776 |
Tips
- Size generators on kVA and starting current. Motor starting can demand 3–7 times running current; soft starters and VFDs reduce it.
- Correct power factor at the source. Individual capacitors on large motors reduce current in the whole distribution system, not just at the main board.
- Don’t over-correct. A leading power factor at light load can cause over-voltage; automatic stepped banks avoid it.
- Check harmonics. Variable-speed drives distort current; plain capacitors can resonate with the network, so use detuned reactors.
- For balanced three-phase loads with star/delta details, use the three-phase power calculator.
Limitations
The calculations assume sinusoidal voltage and current and a balanced three-phase load. With non-linear loads the “true power factor” also includes harmonic distortion, which capacitors do not fix. Breaker, cable and capacitor sizing must follow local wiring regulations and manufacturer data.
Method & assumptions
Power triangle: S² = P² + Q², P = S · cos φ, Q = S · sin φ. Current: single-phase I = S ÷ V; three-phase I = S ÷ (√3 · VLL). Correction capacitor: Qc = P · (tan φ1 − tan φ2). Cable losses scale with I², so raising power factor from 0.8 to 0.95 cuts them by about 29%.
Frequently asked questions
How do I convert kVA to kW?
How do I convert kW to kVA?
How many amps is 100 kVA?
Why are generators rated in kVA instead of kW?
What is a good power factor?
How big a capacitor bank do I need?