How this three-phase power calculator works
Three-phase power supplies almost all industrial loads, large buildings, EV fast and wallbox chargers, heat pumps above a few kilowatts and every power plant. Its arithmetic is simple once you keep two pairs of quantities apart: line voltage and current (what you measure between the wires and in each wire) and phase voltage and current (what each winding or element of the load experiences).
Choose whether you want power from current or current from power, enter the line-to-line voltage and power factor, and pick a star (wye) or delta load. For motors you can enter the shaft output and an efficiency, and the calculator works back to the electrical input. Results include real, apparent and reactive power, line and phase values, impedance per phase, a suggested breaker size, the single-phase current that the same power would need and a table of currents at all standard voltages from 208 V to 33 kV.
The formulas
Worked example: a 32 A outlet at 400 V
The default is a European 400 V supply carrying 32 A per line at a power factor of 0.9, star-connected load:
- Real power: 1.732 × 400 × 32 × 0.9 = 19.95 kW
- Apparent power: 22.17 kVA; reactive power 9.66 kVAr
- Each winding sees 400 ÷ 1.732 = 231 V and carries 32 A (impedance 7.2 Ω per phase)
- A motor at 92% efficiency would deliver 18.4 kW (24.6 hp) at the shaft
- The same 20 kW on a single 230 V phase would need about 96 A, three times the current
How to read the results
- Line current sizes the cables, breakers and contactors.
- Phase values matter for the load itself: winding insulation, heater elements, motor nameplates (e.g. “230 V Δ / 400 V Y”).
- The waveform chart shows the three phase voltages 120° apart; their sum is zero at every instant, which is why a balanced load needs no neutral current.
- The bar chart compares current for your power at standard voltages: higher voltage, lower current, thinner cables.
Standard three-phase voltages
| Line-to-line | Phase (star) | Where |
|---|---|---|
| 208 V | 120 V | US commercial buildings |
| 400 V | 230 V | Europe and most IEC countries |
| 415 V | 240 V | UK, Australia (nominal 400 V ±) |
| 480 V | 277 V | US industry |
| 600 V | 347 V | Canada |
| 690 V | 400 V | Large motors, wind turbines |
| 11–33 kV | 6.4–19 kV | Medium-voltage distribution, wind and solar parks |
Current for common loads at 400 V
| Load | Power | PF | Line current |
|---|---|---|---|
| 11 kW EV wallbox | 11 kW | 0.99 | 16 A |
| 22 kW EV wallbox | 22 kW | 0.99 | 32 A |
| 15 kW heat pump | 5 kW electrical | 0.95 | 7.6 A |
| 7.5 kW motor (IE3, η 90%) | 8.3 kW input | 0.82 | 14.7 A |
| 55 kW motor (η 94%) | 58.5 kW input | 0.86 | 98 A |
Tips
- Balance the phases. Single-phase loads spread unevenly cause neutral current and voltage imbalance; distribute them across L1–L3.
- Check the motor nameplate connection: a “230/400 V” motor must be star-connected on a 400 V network, delta-connected on 230 V.
- Star–delta starting reduces starting current to about one third by starting in star and switching to delta.
- Account for power factor with the kVA to kW calculator, and use Ohm’s law for single elements.
- Breaker sizing shown here is only a rule of thumb; cable size, length, grouping and local code take precedence.
Limitations
The model assumes a balanced, sinusoidal three-phase system. Unbalanced loads, harmonics from drives and rectifiers, voltage drop along long cables and motor starting currents require further analysis. Efficiency and power factor of motors vary with load, so use part-load values for oversized motors.
Method & assumptions
Balanced three-phase power: P = √3 · VL · IL · cos φ (equivalently 3 · Vph · Iph · cos φ). Apparent power S = √3 · VL · IL; reactive Q = √(S² − P²). For a motor, electrical input = shaft power ÷ efficiency.
Frequently asked questions
What is the formula for three-phase power?
How many kW is 32 A three-phase?
How many amps is 22 kW three-phase?
What is the difference between star (wye) and delta?
Why is the line voltage 400 V when the phase voltage is 230 V?
Why use three-phase power at all?