Frequency response
The automatic change in generation or load that arrests and corrects a frequency deviation after a sudden imbalance on the grid.
Frequency response is the sequence of automatic and manual actions that restore grid frequency after a disturbance such as the loss of a large generator or interconnector.
- Inertial response (0 to a few seconds): rotating masses release kinetic energy, limiting the rate of change of frequency (see inertia).
- Primary response (seconds to 30 s): generator governors and fast resources raise output in proportion to the deviation. In Continental Europe this is Frequency Containment Reserve (FCR), about 3,000 MW sized for the loss of two large nuclear units.
- Secondary response (30 s to 15 min): automatic generation control returns frequency to nominal and restores scheduled flows (aFRR).
- Tertiary reserves replace the depleted secondary reserves.
Primary response is governed by droop: a 4% droop means the unit moves from zero to full output over a 4% frequency change (2 Hz at 50 Hz).
NERC measures frequency response in MW per 0.1 Hz; the Eastern Interconnection obligation is roughly 1,000 MW/0.1 Hz. With falling inertia, operators have introduced faster products: Great Britain's Dynamic Containment acts within 1 second and is supplied almost entirely by batteries; ERCOT runs Fast Frequency Response at 0.5 s.
Related terms
All terms →- Grid frequency
The rate at which alternating current changes direction on a power system, 50 Hz or 60 Hz, which reflects the instantaneous balance of supply and demand.
- Inertia (grid)
The kinetic energy stored in synchronously rotating generators and motors that resists sudden changes in grid frequency.
- Ancillary services
Services beyond bulk energy that system operators procure to keep the grid stable and secure, such as frequency reserves, voltage control and black start.
- BESS (Battery Energy Storage System)
A complete grid- or site-connected battery installation, including cells, battery management, power conversion, thermal management and controls.
- Grid-forming inverter
An inverter that sets its own voltage and frequency reference, behaving like a voltage source that can stabilise weak grids and provide synthetic inertia.
- Reserve margin
The amount by which available or accredited capacity exceeds forecast peak demand, expressed as a percentage of peak.