Heat flows from warm to cold, through every surface of a building and every gap in it. Insulation slows the flow, and airtightness stops warm air from leaking out. Between them they set how much energy a house needs before you even choose a boiler or heat pump. The European Commission puts buildings at roughly 40% of EU final energy consumption and about a third of energy-related emissions, and most of the buildings that will stand in 2050 are already built. This guide covers the physics, puts each measure into kWh and euros, and shows where your money goes furthest.
The physics: U-values and heat loss
How well a material conducts heat is given by its thermal conductivity λ (W/mK). In a layered building element, each layer has a thermal resistance R = thickness / λ. The U-value is the inverse of the total resistance, surface resistances included. The lower the U-value, the better the insulation.
Fabric heat loss (W) = Σ (U × A) × ΔT Annual heat loss (kWh) = Σ (U × A) × HDD × 24 / 1,000
HDD = heating degree days (K·day)
Heating degree days measure how cold a climate is: about 2,000–2,500 in London and Paris, 3,000–3,500 in Berlin, Warsaw or Bucharest, 3,500–4,000 in Stockholm or Toronto, and 4,500+ in Helsinki or Minneapolis (base 15.5–18 °C depending on the source).
Typical U-values
| Element | Uninsulated / old | Typical 1980s–1990s | Modern code (N & central Europe) | Passive house |
|---|---|---|---|---|
| Solid brick wall (225 mm) | 1.6–2.1 | — | 0.15–0.28 | ≤0.15 |
| Unfilled cavity wall | 1.2–1.6 | 0.5–0.7 (filled) | 0.15–0.28 | ≤0.15 |
| Roof / loft | 2.0–2.5 (none) | 0.3–0.6 | 0.10–0.20 | ≤0.12 |
| Ground floor (solid) | 0.7–1.2 | 0.4–0.7 | 0.15–0.25 | ≤0.15 |
| Single glazing | 4.8–5.8 | — | — | — |
| Double glazing (old, air) | 2.8–3.3 | 2.6–3.0 | — | — |
| Double low-e, argon | — | — | 1.1–1.4 | — |
| Triple glazing | — | — | 0.6–0.9 | ≤0.8 (whole window) |
Common insulation materials
| Material | λ (W/mK) | Thickness for U ≈ 0.20 on a wall | Notes |
|---|---|---|---|
| Mineral wool (glass/rock) | 0.032–0.040 | 160–200 mm | Cheap, non-combustible, vapour open |
| EPS (expanded polystyrene) | 0.031–0.038 | 150–190 mm | Common for external wall insulation |
| XPS | 0.029–0.035 | 140–170 mm | Moisture resistant, for floors and perimeters |
| PIR / PUR boards | 0.022–0.026 | 110–130 mm | Thin, more expensive; combustibility rules apply |
| Wood fibre | 0.038–0.050 | 190–250 mm | Good summer heat protection, vapour open |
| Cellulose (blown) | 0.037–0.042 | 185–210 mm | Recycled newspaper; lofts and timber frames |
| Aerogel blankets | 0.013–0.018 | 65–90 mm | Very expensive; for tight spaces |
| Vacuum insulated panels | 0.004–0.008 | 25–40 mm | Fragile; niche use |
Where the heat goes
In an uninsulated 1960s detached house, losses typically split like this: walls 25–35%, roof 20–25%, ventilation and air leakage 15–25%, windows and doors 10–20%, floor 10–15%. Flats lose much less through the roof and floor because the neighbours act as a buffer. In poorly detailed buildings, thermal bridges (balconies, lintels, wall–floor junctions) add another 5–15%.
Measures ranked by cost-effectiveness
Costs are indicative for Western Europe in 2024–2026; Eastern Europe is often 30–50% cheaper. Savings assume a gas-heated house paying about €0.11/kWh for delivered fuel in a 3,000 HDD climate.
| Measure | U-value change | Cost | Typical heat saved | Simple payback |
|---|---|---|---|---|
| Draught-proofing doors, windows, loft hatch | — | €200–600 | 1,000–2,500 kWh | 2–5 years |
| Loft insulation 100 → 300 mm | 0.40 → 0.14 | €15–30/m² | 1,500–2,500 kWh | 3–7 years |
| Loft insulation 0 → 300 mm | 2.3 → 0.14 | €20–35/m² | 6,000–14,000 kWh | 1–3 years |
| Cavity wall fill | 1.4 → 0.5 | €15–30/m² | 3,000–7,000 kWh | 2–7 years |
| Hot water tank jacket & pipe lagging | — | €30–100 | 300–800 kWh | <2 years |
| Suspended timber floor insulation | 0.8 → 0.25 | €30–60/m² | 1,000–2,000 kWh | 8–15 years |
| External wall insulation (solid walls) | 1.8 → 0.25 | €120–250/m² | 7,000–13,000 kWh | 15–35 years |
| Internal wall insulation | 1.8 → 0.30 | €80–150/m² | 6,000–10,000 kWh | 12–30 years |
| Double → triple glazing | 2.8 → 0.8 | €500–1,000/m² | 1,500–3,000 kWh | 30–60 years |
| Single → modern double glazing | 5.0 → 1.2 | €400–800/m² | 3,000–5,000 kWh | 15–30 years |
On energy savings alone, walls and windows look like poor value. In practice they are usually done alongside façade repairs or window replacements that were due anyway. Then only the marginal cost of the efficiency upgrade counts, and payback gets much shorter. The comfort gains are real too: no cold walls, no draughts, no condensation. Model your own house in the insulation savings calculator.
Worked example: insulating a loft
Take a 1970s bungalow in central Germany with 80 m² of loft floor and 60 mm of old mineral wool (U ≈ 0.55 W/m²K). Climate: 3,300 HDD. Heating: gas boiler with 88% seasonal efficiency at €0.11/kWh.
At €22/m² installed (€1,760), it pays back in about 5.4 years and keeps saving for 40+ years after that. CO₂ saved: 2,952 kWh × 0.202 kg/kWh ≈ 0.6 tonnes/year. With a heat pump at SPF 3.2 and €0.30/kWh instead, the same work would save 812 kWh of electricity, about €244/year.
The degree-day method overstates savings somewhat when internal and solar gains are high. Monitored homes usually achieve 60–90% of the modelled figure, partly because people spend some of the saving on warmer rooms (the “comfort take-back” or rebound effect).
Ventilation and airtightness
The better the fabric, the larger the share of heat lost through air leakage. A blower-door test measures airtightness as n50 (air changes per hour at 50 Pa) or q50 (m³/h·m²). Old houses often score n50 = 6–15. Modern codes ask for about 3–5 without mechanical ventilation, and passive houses for ≤0.6.
n = effective air changes per hour (≈ n50 / 20 for natural infiltration) V = heated volume (m³)
Sealing a 400 m³ house from n50 = 10 to n50 = 4 cuts infiltration from about 0.5 to 0.2 ACH, which saves roughly 0.33 × 0.3 × 400 × 3,300 × 24 / 1,000 ≈ 3,100 kWh/year. The rule is “build tight, ventilate right”. An airtight house needs controlled ventilation: trickle vents and extract fans at the very least, or mechanical ventilation with heat recovery (MVHR), which recovers 75–90% of the heat in the exhaust air.
Moisture, mould and thermal bridges
Insulation moves the dew point inside a wall. Get it wrong and you get condensation, rot and mould. Some ground rules:
- Vapour control on the warm side. Internal insulation needs either a vapour control layer or a capillary-active, vapour-open system (calcium silicate, wood fibre). Never leave a gap behind it.
- Keep solid walls breathable. Historic solid masonry often needs lime-based, vapour-open systems.
- Check exposure before cavity fill. In walls facing driving rain, water can wick across the fill. A survey should check for this.
- Treat junctions. Carry insulation around window reveals and floor junctions so mould has no cold spots to start from.
- Keep ventilation. Do not block air bricks under suspended floors or ventilation in cold roofs.
Insulation and heat pumps
The two work together. Cut a house’s design heat loss from 12 kW to 8 kW and you can fit a smaller unit, often €1,500–3,000 cheaper, and run the radiators at a lower flow temperature, which lifts seasonal efficiency by 10–20%. You don’t need passive-house standard, though. A deep retrofit costing €50,000+ saves less per euro than a heat pump combined with the cheap insulation measures. Compare scenarios in the heat pump calculator and read Heat Pumps Explained.
Subsidies and policy
Most European countries subsidise insulation. Examples include Germany’s BEG programme, France’s MaPrimeRénov’, the UK’s ECO and Great British Insulation Scheme, Italy’s Ecobonus, and national Recovery and Resilience Plan schemes across the EU. The revised EU Energy Performance of Buildings Directive (2024) requires member states to cut average residential primary energy use by 16% by 2030 and 20–22% by 2035, starting with the worst-performing buildings. See what applies in your country on our country pages.
Common mistakes to avoid
- Compressing loft insulation. Mineral wool works by trapping air. Squash it under boards to make storage space and you can halve its performance. Raise the boards on loft legs or use rigid boards above the joists instead.
- Leaving gaps. Heat takes the path of least resistance, so a 5% gap in an insulation layer can raise heat loss through that element by 20–30%. Fit batts tightly, stagger the joints and seal around services.
- Forgetting the loft hatch and pipes. An uninsulated, unsealed hatch acts as a chimney for warm air. Once the loft turns cold, its pipes and tanks need insulating against frost.
- Insulating without ventilation. Blocking trickle vents, air bricks or eaves ventilation to “keep the heat in” traps moisture. Plan the ventilation; don’t leave it to chance.
- Ignoring summer overheating. Well-insulated homes with big south- or west-facing windows can overheat. External shading, night ventilation and roof insulation with high heat capacity (wood fibre, cellulose) keep summer temperatures down.
- Choosing on λ alone. A thin, high-performance board helps where space is tight. Usually, though, the cheapest way to hit a target U-value is a thicker layer of a cheaper material. Compare cost per m² at the target U-value, not price per board.
- Skipping quality checks. Ask for photos before surfaces are closed up, and consider a thermal imaging survey when the job is done. Poor workmanship is the most common reason measured savings fall short of the forecast.
A sensible order of works
- Survey. An energy audit with a blower-door test and thermal imaging (on a cold day) finds the leaks and weak spots.
- Cheap and fast. Draught-proofing, loft insulation, hot water tank and pipe insulation, radiator reflector panels on external walls.
- Medium. Cavity wall fill, suspended floor insulation, secondary glazing.
- Combine with renovations. External wall insulation when the render needs repair, internal insulation when you replaster, new windows when the old ones fail (with careful detailing at the reveals).
- Then the heating system. Size the heat pump to the improved building.
Bottom line
Insulation keeps paying for decades and has no moving parts. Start with airtightness and the loft, which often pay back within five years, and deal with walls and windows when they need work anyway. Take the U-value change, multiply by area and degree days, and you have a decent savings estimate. Or let the insulation savings calculator and heating cost comparison do the maths for your home.
Calculators for this topic
Frequently asked questions
Which insulation measure has the fastest payback?
How thick should loft insulation be?
What is a good U-value for walls?
Can insulation cause damp problems?
Should I insulate before installing a heat pump?
How much heat is lost through each part of a house?
Sources & references
- IEA — Energy Efficiency 2024 and Buildings tracking report
- EN ISO 6946 — Building components and building elements: thermal resistance and thermal transmittance calculation method
- Energy Saving Trust — Home insulation guidance (UK)
- JRC — Energy renovation of buildings in the EU (European Commission Joint Research Centre)
- Passive House Institute — Building criteria
Figures in this guide are typical ranges drawn from the sources above; your own numbers depend on location, prices and equipment. Use the linked calculators for site-specific estimates.