Home energy guide

Home Insulation Guide: U-Values, Costs and Payback by Measure

Which insulation saves most? U-values, heat loss maths, costs per m², payback for loft, wall, floor, windows and airtightness, with worked examples.

Updated 7 min read 1,536 words

Heat flows from warm to cold, through every surface of a building and every gap in it. Insulation slows the flow, and airtightness stops warm air from leaking out. Between them they set how much energy a house needs before you even choose a boiler or heat pump. The European Commission puts buildings at roughly 40% of EU final energy consumption and about a third of energy-related emissions, and most of the buildings that will stand in 2050 are already built. This guide covers the physics, puts each measure into kWh and euros, and shows where your money goes furthest.

The physics: U-values and heat loss

How well a material conducts heat is given by its thermal conductivity λ (W/mK). In a layered building element, each layer has a thermal resistance R = thickness / λ. The U-value is the inverse of the total resistance, surface resistances included. The lower the U-value, the better the insulation.

R_layer = d / λ U = 1 / (R_si + Σ R_layer + R_se)

Fabric heat loss (W) = Σ (U × A) × ΔT Annual heat loss (kWh) = Σ (U × A) × HDD × 24 / 1,000

HDD = heating degree days (K·day)

Heating degree days measure how cold a climate is: about 2,000–2,500 in London and Paris, 3,000–3,500 in Berlin, Warsaw or Bucharest, 3,500–4,000 in Stockholm or Toronto, and 4,500+ in Helsinki or Minneapolis (base 15.5–18 °C depending on the source).

Typical U-values

Element Uninsulated / old Typical 1980s–1990s Modern code (N & central Europe) Passive house
Solid brick wall (225 mm) 1.6–2.1 — 0.15–0.28 ≤0.15
Unfilled cavity wall 1.2–1.6 0.5–0.7 (filled) 0.15–0.28 ≤0.15
Roof / loft 2.0–2.5 (none) 0.3–0.6 0.10–0.20 ≤0.12
Ground floor (solid) 0.7–1.2 0.4–0.7 0.15–0.25 ≤0.15
Single glazing 4.8–5.8 — — —
Double glazing (old, air) 2.8–3.3 2.6–3.0 — —
Double low-e, argon — — 1.1–1.4 —
Triple glazing — — 0.6–0.9 ≤0.8 (whole window)

Common insulation materials

Material λ (W/mK) Thickness for U ≈ 0.20 on a wall Notes
Mineral wool (glass/rock) 0.032–0.040 160–200 mm Cheap, non-combustible, vapour open
EPS (expanded polystyrene) 0.031–0.038 150–190 mm Common for external wall insulation
XPS 0.029–0.035 140–170 mm Moisture resistant, for floors and perimeters
PIR / PUR boards 0.022–0.026 110–130 mm Thin, more expensive; combustibility rules apply
Wood fibre 0.038–0.050 190–250 mm Good summer heat protection, vapour open
Cellulose (blown) 0.037–0.042 185–210 mm Recycled newspaper; lofts and timber frames
Aerogel blankets 0.013–0.018 65–90 mm Very expensive; for tight spaces
Vacuum insulated panels 0.004–0.008 25–40 mm Fragile; niche use

Where the heat goes

In an uninsulated 1960s detached house, losses typically split like this: walls 25–35%, roof 20–25%, ventilation and air leakage 15–25%, windows and doors 10–20%, floor 10–15%. Flats lose much less through the roof and floor because the neighbours act as a buffer. In poorly detailed buildings, thermal bridges (balconies, lintels, wall–floor junctions) add another 5–15%.

Measures ranked by cost-effectiveness

Costs are indicative for Western Europe in 2024–2026; Eastern Europe is often 30–50% cheaper. Savings assume a gas-heated house paying about €0.11/kWh for delivered fuel in a 3,000 HDD climate.

Measure U-value change Cost Typical heat saved Simple payback
Draught-proofing doors, windows, loft hatch — €200–600 1,000–2,500 kWh 2–5 years
Loft insulation 100 → 300 mm 0.40 → 0.14 €15–30/m² 1,500–2,500 kWh 3–7 years
Loft insulation 0 → 300 mm 2.3 → 0.14 €20–35/m² 6,000–14,000 kWh 1–3 years
Cavity wall fill 1.4 → 0.5 €15–30/m² 3,000–7,000 kWh 2–7 years
Hot water tank jacket & pipe lagging — €30–100 300–800 kWh <2 years
Suspended timber floor insulation 0.8 → 0.25 €30–60/m² 1,000–2,000 kWh 8–15 years
External wall insulation (solid walls) 1.8 → 0.25 €120–250/m² 7,000–13,000 kWh 15–35 years
Internal wall insulation 1.8 → 0.30 €80–150/m² 6,000–10,000 kWh 12–30 years
Double → triple glazing 2.8 → 0.8 €500–1,000/m² 1,500–3,000 kWh 30–60 years
Single → modern double glazing 5.0 → 1.2 €400–800/m² 3,000–5,000 kWh 15–30 years

On energy savings alone, walls and windows look like poor value. In practice they are usually done alongside façade repairs or window replacements that were due anyway. Then only the marginal cost of the efficiency upgrade counts, and payback gets much shorter. The comfort gains are real too: no cold walls, no draughts, no condensation. Model your own house in the insulation savings calculator.

Worked example: insulating a loft

Take a 1970s bungalow in central Germany with 80 m² of loft floor and 60 mm of old mineral wool (U ≈ 0.55 W/m²K). Climate: 3,300 HDD. Heating: gas boiler with 88% seasonal efficiency at €0.11/kWh.

Before: 0.55 × 80 × 3,300 × 24 / 1,000 = 3,485 kWh heat/year After (300 mm, U = 0.14): 0.14 × 80 × 3,300 × 24 / 1,000 = 887 kWh Saved heat: 2,598 kWh → gas saved: 2,598 / 0.88 = 2,952 kWh → €325/year

At €22/m² installed (€1,760), it pays back in about 5.4 years and keeps saving for 40+ years after that. CO₂ saved: 2,952 kWh × 0.202 kg/kWh ≈ 0.6 tonnes/year. With a heat pump at SPF 3.2 and €0.30/kWh instead, the same work would save 812 kWh of electricity, about €244/year.

The degree-day method overstates savings somewhat when internal and solar gains are high. Monitored homes usually achieve 60–90% of the modelled figure, partly because people spend some of the saving on warmer rooms (the “comfort take-back” or rebound effect).

Ventilation and airtightness

The better the fabric, the larger the share of heat lost through air leakage. A blower-door test measures airtightness as n50 (air changes per hour at 50 Pa) or q50 (m³/h·m²). Old houses often score n50 = 6–15. Modern codes ask for about 3–5 without mechanical ventilation, and passive houses for ≤0.6.

Ventilation heat loss (W) = 0.33 × n × V × ΔT

n = effective air changes per hour (≈ n50 / 20 for natural infiltration) V = heated volume (m³)

Sealing a 400 m³ house from n50 = 10 to n50 = 4 cuts infiltration from about 0.5 to 0.2 ACH, which saves roughly 0.33 × 0.3 × 400 × 3,300 × 24 / 1,000 ≈ 3,100 kWh/year. The rule is “build tight, ventilate right”. An airtight house needs controlled ventilation: trickle vents and extract fans at the very least, or mechanical ventilation with heat recovery (MVHR), which recovers 75–90% of the heat in the exhaust air.

Moisture, mould and thermal bridges

Insulation moves the dew point inside a wall. Get it wrong and you get condensation, rot and mould. Some ground rules:

  • Vapour control on the warm side. Internal insulation needs either a vapour control layer or a capillary-active, vapour-open system (calcium silicate, wood fibre). Never leave a gap behind it.
  • Keep solid walls breathable. Historic solid masonry often needs lime-based, vapour-open systems.
  • Check exposure before cavity fill. In walls facing driving rain, water can wick across the fill. A survey should check for this.
  • Treat junctions. Carry insulation around window reveals and floor junctions so mould has no cold spots to start from.
  • Keep ventilation. Do not block air bricks under suspended floors or ventilation in cold roofs.

Insulation and heat pumps

The two work together. Cut a house’s design heat loss from 12 kW to 8 kW and you can fit a smaller unit, often €1,500–3,000 cheaper, and run the radiators at a lower flow temperature, which lifts seasonal efficiency by 10–20%. You don’t need passive-house standard, though. A deep retrofit costing €50,000+ saves less per euro than a heat pump combined with the cheap insulation measures. Compare scenarios in the heat pump calculator and read Heat Pumps Explained.

Subsidies and policy

Most European countries subsidise insulation. Examples include Germany’s BEG programme, France’s MaPrimeRénov’, the UK’s ECO and Great British Insulation Scheme, Italy’s Ecobonus, and national Recovery and Resilience Plan schemes across the EU. The revised EU Energy Performance of Buildings Directive (2024) requires member states to cut average residential primary energy use by 16% by 2030 and 20–22% by 2035, starting with the worst-performing buildings. See what applies in your country on our country pages.

Common mistakes to avoid

  • Compressing loft insulation. Mineral wool works by trapping air. Squash it under boards to make storage space and you can halve its performance. Raise the boards on loft legs or use rigid boards above the joists instead.
  • Leaving gaps. Heat takes the path of least resistance, so a 5% gap in an insulation layer can raise heat loss through that element by 20–30%. Fit batts tightly, stagger the joints and seal around services.
  • Forgetting the loft hatch and pipes. An uninsulated, unsealed hatch acts as a chimney for warm air. Once the loft turns cold, its pipes and tanks need insulating against frost.
  • Insulating without ventilation. Blocking trickle vents, air bricks or eaves ventilation to “keep the heat in” traps moisture. Plan the ventilation; don’t leave it to chance.
  • Ignoring summer overheating. Well-insulated homes with big south- or west-facing windows can overheat. External shading, night ventilation and roof insulation with high heat capacity (wood fibre, cellulose) keep summer temperatures down.
  • Choosing on λ alone. A thin, high-performance board helps where space is tight. Usually, though, the cheapest way to hit a target U-value is a thicker layer of a cheaper material. Compare cost per m² at the target U-value, not price per board.
  • Skipping quality checks. Ask for photos before surfaces are closed up, and consider a thermal imaging survey when the job is done. Poor workmanship is the most common reason measured savings fall short of the forecast.

A sensible order of works

  1. Survey. An energy audit with a blower-door test and thermal imaging (on a cold day) finds the leaks and weak spots.
  2. Cheap and fast. Draught-proofing, loft insulation, hot water tank and pipe insulation, radiator reflector panels on external walls.
  3. Medium. Cavity wall fill, suspended floor insulation, secondary glazing.
  4. Combine with renovations. External wall insulation when the render needs repair, internal insulation when you replaster, new windows when the old ones fail (with careful detailing at the reveals).
  5. Then the heating system. Size the heat pump to the improved building.

Bottom line

Insulation keeps paying for decades and has no moving parts. Start with airtightness and the loft, which often pay back within five years, and deal with walls and windows when they need work anyway. Take the U-value change, multiply by area and degree days, and you have a decent savings estimate. Or let the insulation savings calculator and heating cost comparison do the maths for your home.

Calculators for this topic

Frequently asked questions

Which insulation measure has the fastest payback?
Loft (attic floor) insulation and draught-proofing usually come first, often paying back in 2–6 years, with cavity wall insulation close behind. External or internal solid wall insulation and new windows save a lot of energy, but each kWh saved costs more, so payback on energy alone runs to 15–40 years.
How thick should loft insulation be?
The UK and much of Europe now recommend about 270–300 mm of mineral wool or equivalent, which gives a U-value of roughly 0.15–0.16 W/m²K. Topping up from 100 mm to 300 mm cuts heat loss through the loft by about two thirds.
What is a good U-value for walls?
New-build codes in northern and central Europe typically ask for wall U-values of 0.15–0.28 W/m²K. An uninsulated solid brick wall sits at about 1.5–2.1 W/m²K, so insulating it can cut heat loss through the wall by 80–90%.
Can insulation cause damp problems?
Badly done, it can. Internal wall insulation without a proper vapour control layer, blocked ventilation, or cavity fill in walls exposed to driving rain can all lead to condensation and mould. A good installer checks the moisture risk and makes sure the house stays properly ventilated.
Should I insulate before installing a heat pump?
In most cases, yes, at least the cheap measures. Lower heat loss means a smaller heat pump running at a lower flow temperature, and that improves efficiency. There is no need to reach passive-house standard first.
How much heat is lost through each part of a house?
In a typical uninsulated detached house, roughly 25–35% escapes through the walls, 20–25% through the roof, 15–25% through ventilation and draughts, 10–20% through windows and doors, and 10–15% through the floor. The exact split depends on the shape of the building and on what has already been upgraded.

Sources & references

  1. IEA — Energy Efficiency 2024 and Buildings tracking report
  2. EN ISO 6946 — Building components and building elements: thermal resistance and thermal transmittance calculation method
  3. Energy Saving Trust — Home insulation guidance (UK)
  4. JRC — Energy renovation of buildings in the EU (European Commission Joint Research Centre)
  5. Passive House Institute — Building criteria

Figures in this guide are typical ranges drawn from the sources above; your own numbers depend on location, prices and equipment. Use the linked calculators for site-specific estimates.