You can size a grid-tied solar system for the average year. If it underproduces in December, the grid fills the gap and nobody notices. Off-grid, there is no such safety net. The design question stops being “how many kWh per year?” and becomes “what happens on the fifth grey day in a row in the darkest week of winter?” Get that wrong and the batteries run flat, the inverter shuts down, and an expensive bank of cells starts ageing faster. Below is the method professional designers follow (load audit, worst-month sizing, battery autonomy, backup plan), with numbers you can check against your own site.
Step 1: a realistic load audit
Every other number follows from daily energy consumption in watt-hours. Overestimate it and you waste money; underestimate it and you sit in the dark. List every appliance with its power and daily hours of use.
| Appliance | Power (W) | Hours/day | Wh/day |
|---|---|---|---|
| LED lighting (8 lamps) | 6 each | 4 | 190 |
| Efficient fridge-freezer (A-class) | — | — | 400–700 |
| Laptop + router + phone charging | 60 | 6 | 360 |
| Water pump (pressurised) | 600 | 0.5 | 300 |
| Washing machine (cold wash) | — | 1 cycle | 400–600 |
| TV (LED, 43”) | 60 | 3 | 180 |
| Inverter standby | 15–40 | 24 | 360–960 |
| Total | ≈ 2,200–3,300 |
Two items catch most people out. The first is the inverter’s own idle draw. A 3–5 kW inverter can pull 20–40 W around the clock, or 0.5–1 kWh a day, which can be a quarter of a cabin’s entire load. Pick one with a low no-load figure or a search/eco mode. The second is refrigeration: it runs 24 hours a day and uses more in a hot room. Take the annual kWh on the label and divide by 365.
Keep resistive loads off the system: kettles, electric ovens, hair dryers, immersion heaters and electric space heating. A 2 kW heater running six hours uses 12 kWh, more than many off-grid homes use in two days. Cook and heat with gas, wood or a carefully sized heat pump. Our energy unit converter helps translate appliance ratings into daily Wh.
Step 2: size the array for the worst month
At higher latitudes the solar resource swings hugely with the seasons. In central Europe a south-facing panel collects roughly 5–8 times more energy in June than in December. Near the equator the ratio is close to 1. The design month for a year-round off-grid home is usually December (northern hemisphere) or June (southern).
That is lower than the 0.75–0.85 typical of grid-tied systems, for two reasons: energy passes through the battery, and on sunny days the surplus is wasted once the batteries are full.
Steep tilts help in winter. Panels set at latitude plus 10–20° produce more in December and less in summer, when an off-grid system can’t use the extra anyway. Our solar tilt angle calculator gives the best angle for winter-weighted designs. The EU’s PVGIS tool (JRC) has a dedicated off-grid simulation that reports the share of days the battery would be empty.
Typical design-month sun hours (tilted array)
| Location type | Worst-month PSH | Array needed for 3 kWh/day (PR 0.6) |
|---|---|---|
| Northern Europe (UK, Germany, Poland) | 0.8–1.5 | 3.3–6.3 kWp |
| Southern Europe (Spain, Italy, Greece) | 2.5–3.5 | 1.4–2.0 kWp |
| Sub-Saharan Africa, India | 4.0–5.5 | 0.9–1.3 kWp |
| Desert southwest US, Australia | 4.0–5.5 | 0.9–1.3 kWp |
These ranges are indicative. Real values depend heavily on local cloud climate, snow cover and horizon shading. The northern European row shows why many off-grid homes there run a generator in December and January instead of tripling the array.
Step 3: size the battery bank for autonomy
Autonomy is the number of days the battery can run the home with no solar input at all. It is your buffer for runs of overcast weather.
- Days of autonomy: 1–2 days where there is a generator or the climate is sunny; 3–5 days for remote homes with no backup.
- Usable depth of discharge (DoD): 80–95% for LFP; 50% for lead-acid if you want a reasonable life.
- Round-trip efficiency (η): 92–96% for LFP; 75–85% for lead-acid.
- Temperature factor: lead-acid loses 10–25% of capacity near 0 °C; LFP cannot charge below 0 °C without a heater.
Lithium iron phosphate has largely replaced lead-acid in new off-grid systems. It still costs more per nominal kWh up front, but it delivers far more usable energy over its life: 3,000–8,000 cycles at deep discharge, against a few hundred to around 1,500 for most lead-acid batteries cycled at 50%. Per delivered kWh, LFP usually comes out well ahead. See the home battery storage guide for chemistry details.
Step 4: choose the inverter and charge controller
Inverter power. Add up the loads that might run at the same time, then add 25–50% headroom. Check the surge rating for motors: well pumps, fridge compressors and power tools can draw 3–6 times their running power at start-up. Modern electronics and motors need a pure sine wave inverter.
System voltage. Higher battery voltage reduces current and cable losses. Rough guide: 12 V up to about 1 kW of inverter, 24 V up to 2–3 kW, 48 V above that. A 3 kW load at 12 V draws 250 A, which needs cables as thick as a thumb. At 48 V it draws about 63 A.
Charge controller. A maximum power point tracking (MPPT) controller keeps the panels at the operating point that gives the most power and turns excess voltage into charging current. It also allows long series strings at high voltage, which matters when the array sits far from the battery. Size the controller’s current rating for array power ÷ battery voltage plus 25%, and check that the cold-weather open-circuit voltage of the string (it rises by roughly 0.3%/°C below 25 °C) stays under the controller’s maximum input voltage.
Many modern “all-in-one” off-grid inverters put inverter, MPPT controller and generator charger in one box. Wiring is simpler, but you have a single point of failure.
Worked example: a year-round cabin in central Europe
A weekend-plus-holidays cabin becomes a year-round home in the Czech Republic. Load audit: 3.5 kWh/day after choosing efficient appliances and a low-idle inverter. Design month December, with about 1.3 peak sun hours on a 60° tilted array (a reasonable PVGIS-type value for the region; verify for your exact site). Off-grid PR 0.6.
| Design element | Calculation | Result |
|---|---|---|
| Array (no generator) | 3.5 ÷ (1.3 × 0.6) | 4.5 kWp |
| Array (with generator for Dec–Jan) | sized on February, PSH ≈ 2.2 | 2.7 kWp → choose 3 kWp |
| Battery (3 days autonomy, LFP) | 3.5 × 3 ÷ (0.9 × 0.95) | 12.3 kWh nominal |
| Battery (1.5 days, with generator) | 3.5 × 1.5 ÷ (0.9 × 0.95) | 6.1 kWh → choose 7–10 kWh |
| Inverter | pump 0.6 kW + kitchen 1.2 kW + misc 0.5 kW, ×1.4 | 3 kW, 48 V |
| Generator | charger 2–3 kW, ~150–300 h/year | 3–4 kVA petrol or LPG |
The “with generator” design costs roughly half as much and runs the generator for perhaps 150–300 hours a year, mostly in December and January. In summer the 3 kWp array produces many times what the cabin needs. Most of that surplus goes to waste unless you add flexible daytime loads, such as water heating through a dump load or an electric bike charger.
Run your own location through the off-grid solar calculator to see month-by-month surplus and deficit.
Generator backup and hybrid systems
Size a solar-only system for 100% of days in a northern climate and you end up with absurdly large arrays and battery banks. The cheapest design almost always includes a backup source for the last 5–15% of annual energy:
- Petrol or LPG generator with an automatic start signal from the inverter. LPG stores indefinitely and burns cleaner.
- Small wind turbine: wind is often stronger in winter, which complements solar. Worth it only on genuinely windy, exposed sites; see our guide to small wind turbines for homes.
- Micro-hydro: a stream with enough head can produce steadily, day and night, all winter, and beat both. Try the micro-hydro calculator.
Costs and maintenance
Installed costs vary widely by country and by how much of the work you do yourself. Indicative 2024–2026 ranges in Europe for a professionally installed system:
| Component | Indicative cost |
|---|---|
| Solar modules + mounting | €400–900 per kWp |
| MPPT controller / hybrid off-grid inverter (3–5 kW) | €1,000–3,000 |
| LFP battery | €300–700 per kWh usable |
| Cabling, protection, earthing, installation | 20–40% of hardware |
So a 3 kWp, 10 kWh, 3 kW system typically lands between €8,000 and €15,000. Maintenance is light. Keep panels clear of snow and leaves, check the torque on battery terminals and fuse holders once a year, update firmware, and log state-of-charge data so you catch a failing cell group early.
The global picture
Off-grid solar is far more than a cabin-in-the-woods niche. IEA tracking for SDG7 shows around 750 million people still lacked electricity access in the early 2020s, mostly in sub-Saharan Africa. Both the IEA and IRENA see solar home systems and mini-grids as the cheapest way to connect a large share of them. Explore access and generation by country in our country profiles, or click any location in the Energy Explorer to check its solar resource before you design.
Calculators for this topic
Frequently asked questions
How many solar panels do I need to go off-grid?
How big a battery do I need for off-grid solar?
Can I run a heat pump or electric heating off-grid?
Is off-grid cheaper than a grid connection?
MPPT or PWM charge controller?
What battery voltage should an off-grid system use?
Sources & references
- NREL — PVWatts Calculator (solar resource and production modelling)
- European Commission JRC — PVGIS, including the off-grid PV performance tool
- IEA — SDG7 Data and Projections: Access to Electricity
- IRENA — Off-grid Renewable Energy Solutions to Expand Electricity Access
- Sandia National Laboratories — Stand-Alone Photovoltaic Systems: A Handbook of Recommended Design Practices (SAND87-7023)
Figures in this guide are typical ranges drawn from the sources above; your own numbers depend on location, prices and equipment. Use the linked calculators for site-specific estimates.